EH-1250-HB-UD
Central PCS

EH-1250-HB-UD

Central PCS for utility-scale battery storage
Central PCS
Rated power
1250 kW
Battery voltage range
1000–1500 V
Max efficiency
99%
Cooling
Forced air
Configuration

Specifications.

Compare all models →
ParameterEH-1250-HB-UDNotes
AC output power1375 kVA @30℃ · 1250 kVA @45℃
Max. DC voltage1500 V
Battery voltage range1000–1500 V
Max. DC current1403 A
Nominal AC voltage690 V, 3W+PE
AC voltage range607–759 V (adjustable)
Max. AC output current1151 A @30℃ · 1046 A @45℃
Grid frequency50/60 Hz
Harmonic (THDi)<3% (100% load)
Power factor-1 ~ +1
Off-grid unbalanced load100%
Grid functionsVSG · black start
IsolationTransformerless
Max. efficiency99%European 98.5%
Ingress protectionIP65
Operating temperature-40~+60℃ (>45℃ derating)
Max. altitude5000 m (>3000 m derating)
CoolingForced air
CommunicationRS485 / CAN / Ethernet / Bluetooth
Dimensions (W×D×H)675×1250×2350 mm
Weight950 kg
Rated clients only

Options matrix, derating curves & dynamic models

Selectable options with order codes, temperature/altitude derating curves, PSCAD/PSSE model packages.

Request access
Compliance

Certified where you build.

Certification status →
UL 1741IEEE 1547CSA C22.2EN/IEC 62477-1EN 50549UK G98/G99

Question intake Have a question we haven't answered? Leave it here — it goes straight to the overseas sales team and feeds the product FAQ. High-priority questions get a reply within 24 hours.